Electronic IgnitionLegendary Lighting, L.L.C.
Electronic Ignition Gas Light Installation Procedures The Electronic Ignition gas light systems comes with all the components except the transformer. For the lights and system to work, connect the two electric leads to the transformer, connect the gas, mount the light, turn on the natural gas/propane valve and turn on the switch or breaker. Refer to other sheets for mounting procedures. Transformer Legendary Lighting does not supply the transformer therefore; the installer must provide them. Preferably only two lights per transformer. If more than one light is connected to the transformer or more than one transformer is used in a system, maintain the same polarity (+/-) at each connection. If +/- is not maintained, the system will not operate properly and the transformers will burn out. Locate the transformer in an easily accessible location so in the event it needs to be replaced it will be less of a problem and will not require both a plumber and an electrician. Each light requires a minimum of 20 V.A. or watts of input current to function. Use a 24 volt A.C. Class II (magnetic coil) transformer (preferably 40VA). Preferably only two lights per minimum 40VA transformer. Electrical Connection Before plugging the igniter wires together, slide the black shrink tubing over one of these wires. After connecting, slide the piece of shrink tubing to conceal the exposed terminals. Heat the tubing by moving a flame back and forth along the length of the tubing to shrink the tubing. This helps to insulate the connection. Gas Connection Operation Note: Do not connect the system direct to 110 volt. Follow the procedures noted above. Failure to do so will void the warranty.
During the initial installation there are a few points of concern: We make electronic ignition operated lights that can be post mount, wall mount or ceiling mount. The basic electrical components are the same, the configurations might vary according to the mounting system. There are four major components to the system: a transformer, a solenoid valve, an electronic ignition control box and an ignitor/sensor. TRANSFORMER The transformer must be 24 Volt A.C. Class II. Preferably connect no more than two lights per each transformer. That transformer needs to be a minimum or 40 VA (for connecting one or two lights). If problems exist I suggest checking the output of the transformer first. I have seen new transformers out of the box not put out 24 volts. If the output is less than 24 volt, the electronic ignition control system will not function correctly. From the transformer run separate wires to each light (parallel lines not series) and keep polarity the same. SOLENOID VALVE CONTROL BOX IGNITOR/SENSOR |
